ANALOG INPUT MODULE
32 CHANNEL
P72122-4-0788722
Current: 4–20 mA, 0–20 mA
Voltage: 0–10 V, ±10 V, 1–5 V
Resolution: 16-bit
Accuracy: ±0.1% of full scale
24 binary outputs with enclosed relays (NO contacts)
Current carrying capacity of the relays: max. 1 A
Channel-by-channel isolation of the outputs
Module is capable of redundant operation
Monitoring of the module
Counter for switching cycles (channel by channel)
16 analog outputs, output signal 0/4 ... 20 mA,
channel-by-channel configuration
Load: max. 700 Ohm
Monitoring of loads
Channel-by-channel isolation of outputs
Module is capable of redundant operation
Digital communication with field devices according to
HART protocol (Version 5.0 / 5.1)
Monitoring of modules
Data Rate: Up to 12 Mbps
Isolation:1500 V AC
Power Supply: 24 V DC (±10%)
Power Consumption: Typically 5–10 W
Fieldbus Port: 9-pin D-sub or M12 for PROFIBUS
Operating Temperature:
-25°C to +70°C (-13°F to +158°F)
Humidity: 5–95% noncondensing