Input Type:Thermocouple and / or RTD
Input channels:64 fully-isolated channel-to-channe
Input scan rate:1 Second fixed by IOM
Channel bandwidth:0 to 4.7 Hz (-3 dB)
Nominal input range:-20 to +100 millivolts
Temperature stability:+/-20 ppm per deg C max
Long term drift:500 ppm
Output Type:4-20 mA
Output Channels:16
Output Temperature Drift:0.005% of Full Scale/°C
Output Readback Accuracy:±4% of Full Scale
Output Current Linearity:± 0.05% of Full Scale nominal
Directly Settable Output Current Range:0 mA, 2.9 mA to 21.1 mA
Maximum Output Compliant Voltage:16 V
Maximum Open Circuit Voltage:22 V
Extensive self-diagnostics
Optional redundancy
Supplies non-incendive field power
Suitable for Configure / Status for HART devices
HART-capable, multivariable instruments for
fastcollection of control variables
Fast loop scan
Non-Incendive Power
Voltage Rating:24 VDC
Module current rating:430 mA
Operating Temperature:0 to 60 °C
Storage temperature:-40 to 85 °C
Supervisory network type Series:8 PGM is a standard FTE node
Input Channels:32
Galvanic Isolation:1500 VAC RMS or ±1500 VDC
Isolation Technique:Optical (in IOM)
DI Power Voltage Range:18 to 30 VDC
ON Sense Voltage/Current :13 VDC (min) or 3 mA (min)
OFF Sense Voltage/Current :5 VDC (max) or 1.2 mA (max)
Input Impedance:4.2 K
Absolute Delay Across Input Filter and Isolation:5 ms ± 20%
Input Channels:16 Channels
A/D Converter Resolution:16 bits
Input Range:4-20 mA
Normal Mode Rejection Ratio, at 60 Hz:19 dB
Normal Mode Filter Response:Single-pole RC, -3 dB @ 6.5 Hz
Crosstalk, dc to 60 Hz:-60 dB
Maximum Input Voltage:± 30 Volts
Input Scan:Rate 50 ms