In Stock
Fast Shipping Available
General Electric IC694MDL931
· Product image is representative; revision or series may vary. Contact us to request a specific version.
Ships by Saturday, November 28

IC694MDL931

8-point isolated relay output module

Shipping Information

  • For inventory products, we support same day shipping upon payment.
  • For urgent needs, we offer same-day shipping on most items for orders placed before 2:00 PM UTC+8 Simply mention your preferred next-day shipping when place the order, and your order will be prioritized to minimize downtime.
  • For indent items, typical turnaround is 1-3 weeks, depending on parts availability and scarcity.
Customs & Documentation
We prepare clear, order-specific documentation for every international shipment, including the commercial invoice, packing list and available product or compliance documents. Before dispatch, our logistics team confirms the consignee details, declared value, shipping terms and destination requirements with you. Tracking information is provided after shipment, helping your team prepare for import clearance with confidence.
Documents checked before dispatch · Shipment details confirmed · Global tracking provided
Payment
Payment is by bank wire only in RMB/CNY, GBP, EUR or USD. Amikon does not accept credit cards or provide credit terms. Cleared payment is required before shipment unless the written quotation expressly states otherwise.
Product Condition
Factory New These are new and current items that are procured directly from the manufacturer.
New In Sealed Package Parts are new. They have not been used and still have their original package seal intact.
New in Original Package These parts are new. The packages were not originally sealed by their original manufacturer.
Quantity
Mobile *
Country/Region *
E-mail *
Company
Content *
(gif, jpg, jpeg, png, bmp, doc, docx, xls, xlsx, ppt, pdf, csv)
For more information on how your data is processed and stored by Amikong please read our privacy policy.
  • 20+

    years in automation
  • ISO 9001

    certified quality system
  • 12 months

    amikon warranty
  • 2-hour reply

    from your account manager
  • Success Story

    solutions in action
PRODUCT DESCRIPTION

IC694MDL931 8-point isolated relay output module

GE IC694MDL931 is an RX3i isolated relay output module with eight separately commoned circuits. Its contacts comprise four normally closed relays and four Form C relays, allowing the documented AC or DC load connections.

Each circuit is rated up to 8 A resistive under the applicable load and temperature limits. The module uses backplane 5 V and relay-bus 24 V power, provides numbered output indicators and requires external field power; no onboard output fuses are provided.
ACTUAL APPLICATIONS

Application fields for IC694MDL931

GE IC694MDL931 is an RX3i isolated relay output module with eight separately commoned circuits. Its contacts comprise four normally closed relays and four Form C relays, allowing the documented AC or DC load connections.
  • 01 · WATER & WASTEWATER

    Public Water Treatment and Environmental Sanitation

    Public Water TreatmentEnvironmental Wastewater Treatment
  • 02 · METALS

    Ferrous Metallurgy and Nonferrous Mineral Processing

    Ferrous Metallurgical ProcessingNonferrous Mineral Processing
  • 03 · POWER GENERATION

    Thermal Electricity and Hydroelectric Generation

    Thermal Power GenerationHydroelectric Power Generation

Technical specifications for IC694MDL931

  • Product Model
    IC694MDL931
  • Product Parameters
    8-point isolated relay output module
  • In stock
    9 units
  • Manufacturer
    General Electric
  • Output count
    8 isolated outputs
  • Contact arrangement
    4 normally closed and 4 Form C
  • Nominal field voltage
    24 V DC; 120/240 V AC, 50/60 Hz
  • DC switching range
    5-30 V DC; higher-voltage limits in load table
  • AC switching range
    5-250 V AC, 50/60 Hz
  • Resistive current per point
    8 A maximum, subject to thermal/load limits
  • UL total module current
    20 A maximum
  • Minimum load
    10 mA
  • Inrush current
    8 A maximum for one cycle
  • Field-to-backplane isolation
    250 V AC continuous; 1500 V AC for 1 minute
  • Point-to-point isolation
    250 V AC continuous; 1500 V AC for 1 minute
  • ON/OFF response
    15 ms maximum each
  • Output leakage
    1 mA maximum at 250 V AC and 25 deg C
  • 5 V backplane demand
    6 mA with all outputs ON
  • 24 V relay-bus demand
    110 mA with all outputs ON
View all additional

Alternative Names

IC694MDL931 GE PACSystems RX3i 8-point isolated relay output module
SYSTEM & REPLACEMENT CHECK

Information needed before ordering

Three direct checks to secure your system integration and minimize ordering risks.

Information

System integration Replacement check Manuals & support
SYSTEM INTEGRATION

Integrate IC694MDL931 within GE PACSystems RX3i

Install MDL931 in an RX3i I/O slot and wire the actual contact arrangement from GFK-2314. Outputs 1-4 are normally closed; outputs 5-8 provide Form C connections. Each relay has its own common, so commons must not be inferred from a grouped-output module.
Assess the 8 A point limit against load type, ambient temperature and the 20 A UL module total. The normal switching ranges are 5-30 V DC and 5-250 V AC; the higher DC voltages in the manufacturer load-life table have lower permitted currents.
Budget 6 mA at 5 V and 110 mA from the relay 24 V bus with all relays energized. Verify both energized and de-energized contact states, external protection and any inductive-load suppression before returning the outputs to service.

Features:

  • Output count: 8 isolated outputs
  • Contact arrangement: 4 normally closed and 4 Form C
  • GE PACSystems RX3i
Use IC694MDL931 only within the documented GE PACSystems RX3i arrangement and applicable installation instructions.
INTERCHANGEABILITY

Replace IC694MDL931 within GE PACSystems RX3i

Retain MDL931 contact topology when selecting a spare. An eight-point normally-open relay card does not reproduce the four normally-closed plus four Form C circuits.
Identify every individual common and the NC/NO terminals of outputs 5-8 before disconnecting the terminal block. Record load voltage, current and suppression parts, and isolate external field power before handling the wiring.
After installation, test contact states with the CPU commanding both ON and OFF. Recheck load and temperature limitations, including the UL total-current restriction and the manufacturer contact-life table.

Features:

  • Output count: 8 isolated outputs
  • Contact arrangement: 4 normally closed and 4 Form C
  • GE PACSystems RX3i
Use IC694MDL931 only within the documented GE PACSystems RX3i arrangement and applicable installation instructions.
DOCUMENTATION STATUS

Browse the Manuals, Datasheets, Official Documents, Links

Important Notice: The linked files are Amikong-hosted reference documents. Match their product identity and scope to the supplied assembly, and consult the applicable manufacturer instructions before use. Accessories and additional documents are included only when expressly listed in the quotation.

Features:

  • Exact-model technical data for IC694MDL931
  • Document applicability checked against the complete identity
  • Directory links by subcategory and brand
Documentation for IC694MDL931 must match the installed product identity and supplied configuration.

Important notice

Manuals, software, firmware, cables, calibration data and accessories are included only when listed in the quotation. AMIKON is an independent supplier and is not affiliated with or authorised by the manufacturer.
This content has been produced using multiple sources. Takes no responsibility for the accuracy of this information. Always consult the original equipment manufacturer for the most up to date instructions and information.
BUYER INFORMATION

Commercial terms without hidden steps

Your written quote confirms the product identity, price, availability, lead time, warranty and shipping terms before payment.
  • 01

    Shipping & delivery

    Dispatch
    Eligible stock: same / next day
    Carriers
    DHL, FedEx or UPS
    Ship from
    Xiamen, China
    Product size
    Approx. 3.50 x 13.00 x 13.50 cm
    Net weight
    Approx. 0.34 kg
  • 02

    Payment & customs

    Payment
    Bank transfer (T/T)
    Currencies
    USD · EUR · GBP · RMB
    Credit cards
    Not accepted
    HS reference
    8538900000
    Origin
    United States
  • 03

    Warranty & returns

    Warranty
    12 months from AMIKON
    Inspection
    Label, condition and packing checks
    Returns
    Prior RMA authorisation required
    Compatibility
    Confirm before order
    OEM warranty
    Does not apply
Your written quote confirms the product identity, price, availability, lead time, warranty and shipping terms before payment.
  • Part checked

    Full suffix recorded
  • Condition checked

    Label and appearance
  • Packing checked

    Antistatic protection
  • Tracking supplied

    Established couriers
  • Sandy Lin

    Dedicated account manager · 15+ years
FREQUENTLY ASKED QUESTIONS

Questions buyers ask about IC694MDL931

Direct answers about identity, compatibility, stock, warranty, payment and shipping.
  • Are all eight MDL931 contacts normally open?

    No. The module contains four normally-closed circuits and four Form C circuits, each with a separate common.
  • How are outputs 5 through 8 wired?

    They provide Form C contacts with separate normally-closed, common and normally-open terminals as shown in GFK-2314.
  • Does the 8 A rating apply at every DC voltage?

    No. The nominal DC switching range is 5-30 V, and the load table reduces current at higher DC voltages. Load type and temperature also matter.
  • What total current limit applies to UL installations?

    The manufacturer specifies 20 A maximum per module for UL installations, in addition to point and thermal restrictions.
  • Is relay energization supplied from the field circuit?

    The relay coils use the backplane relay 24 V bus. External AC or DC power operates the connected field loads.
  • Which response time should be allowed for contact changes?

    The specified ON and OFF response times are each 15 ms maximum.
  • Which contact detail prevents an incorrect distributor substitution?

    The quotation must preserve the four NC plus four Form C arrangement, not merely state eight relay outputs.
  • What load information should an MDL931 spare order include?

    State AC or DC voltage, resistive or inductive load, required current and simultaneous energized outputs so the applicable limits can be checked.
READY TO VERIFY YOUR PART?

Get a IC694MDL931 quote with price, lead time and revision check.

Trusted by 5,000+ plants worldwide | Backed by our vast inventory of top-tier control parts, drives and servo motors, fast shipments are dispatched to cover your urgent needs. ABOUT US >>
Disclaimer: Amikon Limited sells new and surplus products and develops channels for purchasing such products. Amikon Limited is not an authorized surplus dealer or affiliate for the Manufacturer of this product. The product may have older date codes or be an older series than that available direct from the factory or authorized dealers. Because Amikon Limited is not an authorized distributor of this product, the Original Manufacturer's warranty does not apply. Amikon Limited is not an authorized distributor, dealer, or representative of the products displayed on this website. All product names, trademarks, brands, and logos used on this website are the property of their respective owners. The description, explanation, or sale of products with these names, trademarks, brands, and logos is for identification purposes only and is not intended to indicate any association with or authorization from any rights holder.