BUS INTERFACE MASTER MODULE
16-Pointor8-Poin
KS Cable Interface Adapter
for Analog 16-channel
with ISA Standard G3 option
Connecting with AEA4D
Connectingwith MUB,TE16
Current Input Module
16, isolated
4 to 20 mA
270 Ω (20 mA) to 350 Ω (4 mA)
±16 µA
230 mA (5 V DC), 540 mA (24 V DC)
Digital Output Module
±36 V
1 MΩ or more
500 Ω or less
±100 mV, ±0.3 % of full scale
Max. ±6.4 mV/ °C, ±0.02 %/ °C
15 bits/0-32 V
Power Supply Module
Input Voltage: 100–120 V AC
Input Frequency: 50/60 Hz
Maximum Power Consumption: 200 VA
Output Voltage: Typically 24 V DC
Operating Temperature: -10°C to +55°C (14°F to 131°F)
Storage Temperature: -25°C to +70°C (-13°F to 158°F).
Humidity: 5–95% RH (non-condensing)
Digital Output Module
Number of outputs 8-channel, module isolation
Output voltage 24 V DC
Output voltage drop 1 V maximum
External power supply rating 24 V DC, 5 A minimum
External power supply 24 V DC +20 %/–10 %
Output format Current source
Maximum load current 0.6 A/output line
Minimum load current 35 mA
Load resistance range 40 to 685 Ω
Output response time 30 ms maximum
Digital Output Module
Number of outputs 8-channel, module isolation
Output voltage 24 V DC
Output voltage drop 1 V maximum
External power supply rating 24 V DC, 5 A minimum
Maximum leak current at output offstatus 1.6 mA
Output format Current source
Maximum load current 0.6 A/output line
Minimum load current 35 mA
Load resistance range 40 to 685 Ω
Output response time 30 ms maximum
20x11x7.6cm 0.3
Digital Output Module
Number of outputs 8-channel, module isolation
Output voltage 24 V DC
Output voltage drop 1 V maximum
External power supply rating 24 V DC, 5 A minimum
Output format Current source
Maximum load current 0.6 A/output line (4.8 A in total output lines)
Minimum load current 35 mA
Load resistance range 40 to 685 Ω
Output response time 30 ms maximum
Bus Coupler Module
Function: ESB bus master interface function
Number of connectable units: 9 units maximum
Transmission speed: 128 Mbps
Transmission distance: 10 m maximum
Current consumption: 0.5 A
V-NET Coupler Module
Input Voltage: 24 V DC
Power Consumption: Estimated 10–15 W
Operating Temperature: -10°C to +55°C (14°F to 131°F)
Humidity: 5–95% RH (non-condensing)
Contact Input Module
POWER SUPPLY MODULE
STLYE S2
16 points
OFF signal 4.5 to 25 V DC,
ON signal ± 1 V DC, 200 Ω or less
Copyright Notice © 2004-2024 amikong.com All rights reserved
Disclaimer: We are not an authorized distributor or distributor of the product manufacturer of this website, The product may have older date codes or be an older series than that available direct from the factory or authorized dealers. Because our company is not an authorized distributor of this product, the Original Manufacturer’s warranty does not apply.While many DCS PLC products will have firmware already installed, Our company makes no representation as to whether a DSC PLC product will or will not have firmware and, if it does have firmware, whether the firmware is the revision level that you need for your application. Our company also makes no representations as to your ability or right to download or otherwise obtain firmware for the product from our company, its distributors, or any other source. Our company also makes no representations as to your right to install any such firmware on the product. Our company will not obtain or supply firmware on your behalf. It is your obligation to comply with the terms of any End-User License Agreement or similar document related to obtaining or installing firmware.