Digital Input Module
Points:4, commoned-return, DC-coupled
Output current range:
4–20 mA output, controlled
0–22 mA over-range
0 mA output capability (step function <2 mA)
Type:TMR
Resolution:12 bits
Diagnostic:Forced-switch diagnostic (FSD)
Over-range protection:36 V DC, continuous
Digital Input Module
Points:32, commoned
Nominal input voltage:24 V DC
Operational voltage range:15–30 V DC
Absolute maximum input voltage:33 V DC
Absolute maximum reverse input voltage:–0.6 V DC
Input delay:<10 ms, On to Off or Off to On
ADC scan time:<1 ms for all 32 points
Digital Output Module
Points:16, commoned
Nominal output voltage:24 V DC
Operational voltage range:15–30 V DC
Absolute maximum output voltage:33 V DC
Absolute maximum reverse input voltage:–0.6 V DC
Leakage to load (Off-state):<1 mA
On-state voltage drop:<1 V DC @ 1.5 A
Loop-back scan time:<1 ms for all 16 points
ANALOG INPUT MODULE
Points:32, commoned
Nominal input current:4–20 mA DC
Operational current range:2–22 mA DC
Absolute maximum field voltage:33 V DC
Absolute maximum input current:50 mA DC
Input bandwidth (3dB):16 Hz
Source impedance:180 Ω
Resolution:12 bits
Absolute error:0.15% of full scale (20 mA)
Diagnostic:Force-to-value diagnostic (FVD)
Scan time:<1 ms for all 32 points
Contact And Non-Contact Thermometer
Offers a distance-to-spot ratio of 50:1
Works with most K-type thermocouples
Allows easy access to advanced features
with soft-key buttons and graphical display
Captures up to 99 points of data for
quick downloading to a PC through the USB connection
Quickly identifies problems with MIN, MAX, AVG, and DIF functions
Easily adapts to lighting conditions with a two-level backlight
Handheld Digital Multimeter
DBV / dBm measurement
1 μV resolution in DC mV range
Current measurement 20 A
(30 seconds momentary, 10 A continuous)
Peak capture function to record transients as fast as 250 μs
Continuity / Conductance / Capacitance
Resistance and continuity
Duty cycle & pulse width measurement
Min / Max / Average with Time Stamp to record signal fluctuations
Real time and elapsed time modes
CAT III 1000 V / CAT IV 600 V safety rated
Analog Input Module
Points:32, commoned
Nominal input current:4–20 mA DC
Operational current range:2–22 mA DC
Absolute maximum field voltage:33 V DC
Absolute maximum reverse field voltage:– 0.6 V DC
Absolute maximum input current:50 mA DC
Input bandwidth (3dB):16 Hz
Source impedance:180 Ω
Resolution:12 bits
Absolute error:0.15% of full scale (20 mA)
Diagnostic:Force-to-value diagnostic (FVD)
Digital Input Module
Points:32, commoned
Nominal input voltage:24 V DC
Operational voltage range:15–30 V DC
Absolute maximum input voltage:33 V DC
Absolute maximum reverse input voltage:–0.6 V DC
Input delay:<10 ms, On to Off or Off to On
ADC scan time:<1 ms for all 32 points
Analog Output Module
Type:TMR
Resolution:12 bits
Diagnostic:Forced-switch diagnostic (FSD)
Points:4, commoned-return
Output current range:4–20 mA output, controlled
External loop power:32 V DC, maximum24 V DC, nominal
Digital Output Module
Points:16, commoned
Nominal output voltage:24 VDC
Specified operational voltage range:15 to 30 VDC
Absolute maximum output voltage:33 VDC
Absolute maximum reverse input voltage:– 0.6 VDC
Leakage to load (Off state):<1 mA
Diagnostic glitch duration <2 ms, maximum:500 Ps, typical
On state voltage drop:<1.0 VDC @ 1.5 A

Copyright Notice © 2004-2024 amikong.com All rights reserved
Disclaimer: We are not an authorized distributor or distributor of the product manufacturer of this website, The product may have older date codes or be an older series than that available direct from the factory or authorized dealers. Because our company is not an authorized distributor of this product, the Original Manufacturer’s warranty does not apply.While many DCS PLC products will have firmware already installed, Our company makes no representation as to whether a DSC PLC product will or will not have firmware and, if it does have firmware, whether the firmware is the revision level that you need for your application. Our company also makes no representations as to your ability or right to download or otherwise obtain firmware for the product from our company, its distributors, or any other source. Our company also makes no representations as to your right to install any such firmware on the product. Our company will not obtain or supply firmware on your behalf. It is your obligation to comply with the terms of any End-User License Agreement or similar document related to obtaining or installing firmware.