3300 XL 8 mm Proximity Probes
330102 3300 XL 8 mm Probe
3/8-24 UNFthread, with armor
Minimum unthreaded length: 0.0 in
Minimum case length: 7.0 in
10 1.0 meter (3.3 feet)
02 Miniature coaxial ClickLocconnector
standard cable
05 CSA, ATEX, IECEx Approvals
3300 XL 8 mm Proximity Probes
330101 3300 XL 8 mm Probe
3/8-24 UNFthread, without armor
20 2.0 meters (6.6 feet)
02 Miniature coaxial ClickLocconnector
standard cable
05 CSA, ATEX, IECEx Approvals
Power Supply Unit 24/5 Vdc, 16A (conformal coated)
Operating temperature:-5°C-+70°C (+23°F-+158°F)
Storage temperature: -40°C-+85°C (-40°F-+185°F)
Relative humidity: 10-95% (non condensing)
Approvals:CE, TUV, UL, CSA, FM
24 V supply voltage: 24 V DC -15%-+30%
24 V supply current:
< 6 A at 24 Vin (16 A load)
< 7 A at 20.4 Vin (16 A load)
Inrush current: < 5 A at 24 Vin
Hold-up time: < 1ms
Safety Manager System Module
5 V supply voltage: 5 V DC ± 5%
5 V supply currentLmax 1.2A
Operating temperature:
-5°C - +70°C (+23°F - +158°F)
Storage temperature:
-40°C - +85°C (-40°F - +185°F)
Relative humidity: 10 - 95% (non condensing)
Hazardous Gas Sensor
DETECTION SENSOR
HAZARDOUS GAS
REVISED TO 350800-01-006-00
15 MV / % LEL SENSITIVITY
FLAMEPROOF AND IP66
Scalance XB005 Unmanaged Ethernet Module
SCALANCE XB005
unmanaged Industrial Ethernet Switch
for 10/100 Mbit/s
forsetting up small star and line topologies
LED diagnostics, IP20
24 V AC/DCpower supply
with 5x 10/100 Mbit/s twisted pair ports with
RJ45 sockets; Manualavailable as a download
Digital Input Module - High Feature
SIMATIC DP
5 ELECTRON. MODULES
FOR ET 200S
4 DI HIGHFEATURE 24V DC
15 MM WIDTH WITH PARAM
F. INPUT DELAYDIAGNOSIS F
ENCODER SHORT- CIRCUIT W. LED SF
SIMATIC ET 200SP DI 8X24VDC HF
SIMATIC ET 200SP
Digital input module
DI 8x 24 V DC High Feature
input type 3(IEC 61131)
suitable for BU typeA0
color code CC01, input delay 0.05..20 ms
Channel diagnostics for: Encoderpower supply short circuit
wire break, supply voltage, channel fault LED
ControlLogix 20MB controller
CONTROLLER
CONTROLLOGIX
20 MB USER MEMORY
USB PORT
1 GB ETHERNET PORT
250 ETHERNET/IP DEVICES
4 CHARACTER ALPHA/NUMERIC DISPLAY
Analog Output Module -High Feature
SIMATIC DP
ELECTRONIC MODULE
2 AO I HIGH FEATURE FORET 200S
15 MM WIDE
CYCLE TIME PER MODULE: 0.5MS, +/-20MA
15 BIT + SIGN, 4 .. 20MA; 15 BIT
OPERATIONAL LIMITS
+/-0.05% WITH LED SF
SPEED TRANSDUCER MODULE
Magnetic pickup (MPU) or proximity probe
Frequency range: 1Hz to 10kHz
Input sensitivity: 50mV RMS minimum
Accuracy: ±0.1% of reading ±1 RPM
Analog Output:4-20mA
Load capacity: ≤500Ω
Power Supply:24V DC ±10% (standard)
3300 NSv Proximity Probes
330902 3300 NSv Probe
1/4-28 UNF thread,with armor
Minimum unthreaded length: 0.0 in
Minimum case length: 0.8 in
10 1.0 meter (39 in)
02 Miniature coaxial ClickLoc connector
standard cable
05 Multiple Approvals
3300 XL 8 mm Proximity Probes
330101 3300 XL 8 mm Probe
3/8-24 UNFthread, without armor
Minimum unthreaded length: 0.0 in
Minimum case length: 3.0 in
10 1.0 meter (3.3 feet)
01Miniature coaxial ClickLocconnector
with connectorprotector, standard cable
00 Not required
Copyright Notice © 2004-2024 amikong.com All rights reserved
Disclaimer: We are not an authorized distributor or distributor of the product manufacturer of this website, The product may have older date codes or be an older series than that available direct from the factory or authorized dealers. Because our company is not an authorized distributor of this product, the Original Manufacturer’s warranty does not apply.While many DCS PLC products will have firmware already installed, Our company makes no representation as to whether a DSC PLC product will or will not have firmware and, if it does have firmware, whether the firmware is the revision level that you need for your application. Our company also makes no representations as to your ability or right to download or otherwise obtain firmware for the product from our company, its distributors, or any other source. Our company also makes no representations as to your right to install any such firmware on the product. Our company will not obtain or supply firmware on your behalf. It is your obligation to comply with the terms of any End-User License Agreement or similar document related to obtaining or installing firmware.