Foundation Fieldbus FF-H1 Communication Module
Interface Foundation fieldbus 4 ports
Transmission speed 31.25 kbps
field to system: 1500 V AC/minute
Max. 48 points/segment
Max. 32 units per segment
LAS function, Clock master function
Digital Output Module
DIGITAL INPUT MODULE
32 CHANNEL
24 VDC
ISOLATED
50 MA
PULSE WIDTH OUTPUT FUNCTION
TIME-PROPORTIONAL OUTPUT FUNCTION
STATUS DISPLAY
NO EXPLOSION PROTECTION
Digital Input Module
Number of input channels:64
Rated input voltage:24 V DC
Input ON voltage:20 to 26.4 V DC
Input OFF voltage :5.0 V DC or less
Input current :2.5 mA±20 % / channel
Maximum allowable input voltage:30.0 V DC
Input response time :8 ms or less
Minimum ON detection time:20 ms
Maximum ON/OFF cycle:25 Hz
Maximum current consumption:500 mA (5 V DC)
Digital Input Module
Number of inputs 16-channel, module isolation
Input signa:
No-voltage contact
ON: 1 kΩ maximum
OFF: 100 kΩ minimum
Input current 6 mA ± 20 %
Contact rating 24 V DC +20 % / -10 %
Input response time 40 ms maximum
Digital Output Module
Number of outputs 8-channel, module isolation
Output voltage 24 V DC
Output voltage drop 1 V maximum
External power supply rating 24 V DC, 5 A minimum
Maximum leak current at output offstatus 1.6 mA
Output format Current source
Maximum load current 0.6 A/output line
Minimum load current 35 mA
Load resistance range 40 to 685 Ω
Output response time 30 ms maximum
Trusted Expander Module
Input Voltage: 24 VDC
Operating Temperature: Typically 0°C to +60°C (32°F to 140°F)
Storage Temperature: -40°C to +85°C (-40°F to 185°F)
Humidity: 5% to 95% relative humidity
Control Unit
Supply Voltage:24 V DC
Current Consumption:Around 300 mA
Operating Temperature Range:-10°C to +55°C
Storage Temperature Range:-40°C to +70°C
Humidity:5% to 95%, non-condensing.
Sync Board
Input Voltage:24V DC
Temperature Range:-20°C to 60°C
Storage Temperature:-40°C to 85°C
Humidity:5% to 95% (non-condensing)

Copyright Notice © 2004-2024 amikong.com All rights reserved
Disclaimer: We are not an authorized distributor or distributor of the product manufacturer of this website, The product may have older date codes or be an older series than that available direct from the factory or authorized dealers. Because our company is not an authorized distributor of this product, the Original Manufacturer’s warranty does not apply.While many DCS PLC products will have firmware already installed, Our company makes no representation as to whether a DSC PLC product will or will not have firmware and, if it does have firmware, whether the firmware is the revision level that you need for your application. Our company also makes no representations as to your ability or right to download or otherwise obtain firmware for the product from our company, its distributors, or any other source. Our company also makes no representations as to your right to install any such firmware on the product. Our company will not obtain or supply firmware on your behalf. It is your obligation to comply with the terms of any End-User License Agreement or similar document related to obtaining or installing firmware.