Program Memory:
128 kB Flash memory
64 kB RAM
Data Memory:
16 kB non-volatile memory for retain data
Power Supply Voltage: 24 V DC (±20%)
Operating Temperature:
Standard range: -25°C to +60°C
Storage Temperature:
-40°C to +85°C
PROFIBUS DP PROFIBUS-DPV1 fieldbus interface.
Supervisory functions of I/O ModuleBus
Isolated power supply to I/O modules
OSP handling and configuration
Input power fused
Hot Configuration In Run
HART pass-through
8 channels for RTD
(Pt100, Cu10, Ni100 and Ni120 and resistor) inputs
3-wire connection to RTDs
14 Bit resolution
Inputs are monitored for open-circuit,
shortcircuit and has a input grounded sensor
10 Mbps or 100 Mbps Ethernet network transmission
Communicates with up to 64 field devices
I/O software driver a library of available protocols
Up to 2000 DCI block connections
Integrates field device data into a
Foxboro DCS control database using Ethernetconnectivity
Field mounted
Class G3 (harsh) environments
Current: 4–20 mA
Voltage: 0–10 V, ±10 V
current: 750 ohms
voltage: 10 kΩ
Operating Voltage: 24 V DC (nominal)
Power Consumption: Approximately 4 W per module
Nominal Supply Voltage Range: 20.4 V to 27.6 V DC
Current Consumption: Typically 200 mA
Product type : 32 Inputs
Non CE Compliant Part Number : N/A
CE Compliant Part Number : 51304362-150
IOP Type: Low Level Multiplexer (LLMux)
LLMux Assembles: LLMux IOP Conformally Coated
Resolution 16-bit resolution
Operating Voltage 24 VDC
Operating Temperature 0°C to 60°C
Storage Temperature -40°C to 85°C
Humidity 5% to 95% non-condensing
Input Type Current (2-wire or self-powered transmitters)
Input Channels 16 Channels (16 Single Ended)
Common Mode Rejection Ratio, dc to 60 Hz 70 dB
A/D Converter Resolution 16 bits
Input Range 4-20 mA (through 200 Ω)
Normal Mode Rejection Ratio, at 60 Hz 20 dB
Normal Mode Filter Response Single-pole RC, -3 dB @ 6.0 Hz
Maximum Normal Mode Input ± 30 Volts
8 isolated independent
pulse input channels
10 Hz to 25 kHz
4 isolated independent
0 to 20.4 mA dc analogoutput channels
735 Ohms
18.6 V nominal at 20 mA dc
at I/O field terminals
±0.05% of span (@25°C)
100 ppm/°C
SDCS-PIN-51-COAT
Analog Inputs (AI):0–20 mA/4–20mA
PT100/RTD temperature
Channel Capacity: 8/16 channels
Resolution: ≥16-bit ADC
Sampling Rate: up to 1 kHz
Accuracy: ±0.1% of full scale
Operating Temperature: -25°C to +70°C
Humidity: Up to 95% non-condensing.
OUTPUT MODULE 40CHANNEL
DIGITAL 24/48VDC TRUSTED
Output Channels: 16
Output Voltage Range: 5-60V DC
On-State Resistance: <0.5Ω
Off-State Leakage: <10μA
Backplane Power: +5V DC
Field Power: 24V DC nominal
Analog Inputs: 2 channels
Analog Outputs: 2 channels
Digital Inputs: 6 channels
Digital Outputs: 3 relay outputs
Operating Temperature Range: -10°C to +55°C
Storage Temperature Range: -40°C to +70°C
Humidity: 5%-95% (non-condensing)
Protection Level: IP20
Analog: 0–10 VDC or 4–20 mA
Response Time: ≤1 ms
Accuracy: ±0.1% of full scale
Supply Voltage: 24 VDC (±10%) or 100–240 VAC
Power Consumption: ≤10 W (typical)
Operating Temperature: 0°C to +55°C (32°F to +131°F).
Humidity: 5–95% non-condensing.
Communication Protocol:MasterBus 300 (MB 300)
Ethernet Ports:2 x RJ45 (8-pin)
Transmission Speed:10 Mbit/s
Data Rate:200 Datasets/s
Operating Temperature:Up to 55°C
Protection Class:IP20 (according to EN60529, IEC 529)
Power Consumption:150 mA @ 24 VDC
8 channels for 0...20 mA, 4...20 mA
0...10 V or 2...10 V d.c.
single ended unipolar inputs
1 group of 8 channels isolated from ground
12 Bit resolution
Input shunt resistors protected to 30 V by PTC resistor
Analog inputs are short circuit secured to ZP or +24 V
The input withstand HART communication.
Safe digital output module (24 Vdc, 0.55 A, 8 channels)
Relais + channel 8: approx. 200 mA
Read back circuit:
< 110 mA (single SDI-1624)
< 210 mA (redundant SDI-1624)
max. 275 mA at Vmax
DIN EN rails: TS32 / TS35 × 7.5
Max switched power: 150 Watts
RAM: 512 MB of RAM
Operating Temperature: -5°C to +55°C
Storage Temperature:-25°C to +70°C
Humidity: humidity from 5% to 95%, non-condensing.
Power Supply: 24 VDC
Number of channels 8
Resolution 12 bits
Guaranteed accuracy
0.10% [0.045 (Rcold/Rspan)]%
Temperature coefficient 10ppm/℃
Input impedance
100 M OHM50 K OHM in power down
Module power 3.6 W typical;
4.2 W maximum
Operating temperature range 0 to 60℃ (32℉to 140℉)
Storage temperature range -40℃ to 85℃ (-40℉ to 185℉)
Humidity (non-condensing) 0 to 95%
Input Type
Thermocouple, RTD, and linear millivolts
32 galvanically isolated
250 Vac Peak or ±250 Vdc
14 bits
TC types J, K, E, T, B, S, R, RP: 10 µV per bit
100 Ω and 120 Ω RTDs: 64 mΩ per bit
10 Ω RTD: 8 mΩ per bitLinear mV
sensors: 20 µV per bit