Analog Input Module
Extensive self-diagnostics
Optional redundancy
Supplies non-incendive field power
(No externaluser supplied power)
Suitable for Configure / Status for HART devices
HART-capable, multivariable instruments
for fastcollection of control variables
Fast loop scan
Non-Incendive Power
Analog Input Module
AI IOTA
Extensive self-diagnostics
Optional redundancy
Supports either Single Ended / DifferentialInputs
HART-capable, multivariable instruments
and multiplemodems for fast collection of control variables
Fast loop scan
Power Adapter Terminal Assembly
Power Input:24V DC
Current Capacity:5A max
Operating Temperature:
-10°C to 60°C (14°F to 140°F)
Storage Temperature:
-40°C to 85°C (-40°F to 185°F)
Humidity Tolerance:5% to 95% non-condensing
Five-slot File Power Supply
TDC 3000
Five-slot File Power Supply
Chassis Power Supply
CE-compliant
Standard 3-pin connector
System PSU 115/230VAC 24Vdc 50A CC,UL508
Power requirements : 110-240 Vac
Power consumption at no load : 13 W
Input frequency range : 47-63 Hz
Storage temperature : –25°C—+85°C (–13°F—+185°F)
Operating temperature : –5°C—+70°C (23°F—+158°F)
Inrush current : < 15 A
Output voltage : 25 Vdc or 28 Vdc; dual overvoltage protection
Ripple and noise : < 40 mVpp
Hold-up time : 100 ms at full load
Output voltage setting : 25 Vdc
Efficiency at 230 Vac : >87%
Safe Digital Input FTA
Safe digital input FTA
24/48 V DC, NAMUR, 16 channels
Sixteen channels ,eight channels with a 250 mA fuse
canbe connected to the TSDI-16UNI module
via a system interconnection cable (SICC-0001/Lx)
SIC connector on the FTA module
connects to a (redundant pair of) SDIL-1608module(s)
DC/DC converter
CONVERTER
1 AMP
DC/DC converter
24 V DC to 30 V DC / 1 A converter
30 V DC / 1 A to other fieldtermination assemblies (FTAs)

Copyright Notice © 2004-2024 amikong.com All rights reserved
Disclaimer: We are not an authorized distributor or distributor of the product manufacturer of this website, The product may have older date codes or be an older series than that available direct from the factory or authorized dealers. Because our company is not an authorized distributor of this product, the Original Manufacturer’s warranty does not apply.While many DCS PLC products will have firmware already installed, Our company makes no representation as to whether a DSC PLC product will or will not have firmware and, if it does have firmware, whether the firmware is the revision level that you need for your application. Our company also makes no representations as to your ability or right to download or otherwise obtain firmware for the product from our company, its distributors, or any other source. Our company also makes no representations as to your right to install any such firmware on the product. Our company will not obtain or supply firmware on your behalf. It is your obligation to comply with the terms of any End-User License Agreement or similar document related to obtaining or installing firmware.