Amikon Limited comprehensive Honeywell automation solutions, specializing in the supply of the following core product lines:
Experion PKS ,TDC 3000, TDC 2000, Distributed Control Systems,Experion LS,Safety Manager™ Safety Instrumented Systems,FSC™ (Fail Safe Controller) Safety Systems Additionally,we specialize in providing critical Obsolete Parts for discontinued Honeywell equipment across all legacy systems.
Whether you require components for specific platforms (such as Experion PKS or TDC 3000), or need to source replacement or obsolete parts based on equipment functionality, please Email now: info@amikon.cn.
We are committed to sourcing the Honeywell process control products you need.
Amikon Limited comprehensive Honeywell automation solutions, specializing in the supply of the following core product lines:
Experion PKS ,TDC 3000, TDC 2000, Distributed Control Systems,Experion LS,Safety Manager™ Safety Instrumented Systems,FSC™ (Fail Safe Controller) Safety Systems Additionally,we specialize in providing critical Obsolete Parts for discontinued Honeywell equipment across all legacy systems.
Whether you require components for specific platforms (such as Experion PKS or TDC 3000), or need to source replacement or obsolete parts based on equipment functionality, please Email now: info@amikon.cn.
We are committed to sourcing the Honeywell process control products you need.
Five-Slot and Ten-Slot Module
configured to perform various functions,
Universal Stations in the TPS system.
Each module occupies a specific address (node)
on the Local Control Network (LCN).
Input Type:Thermocouple and / or RTD
Input channels:64 fully-isolated channel-to-channe
Input scan rate:1 Second fixed by IOM
Channel bandwidth:0 to 4.7 Hz (-3 dB)
Nominal input range:-20 to +100 millivolts
Temperature stability:+/-20 ppm per deg C max
Long term drift:500 ppm
Output Type:4-20 mA
Output Channels:16
Output Temperature Drift:0.005% of Full Scale/°C
Output Readback Accuracy:±4% of Full Scale
Output Current Linearity:± 0.05% of Full Scale nominal
Directly Settable Output Current Range:0 mA, 2.9 mA to 21.1 mA
Maximum Output Compliant Voltage:16 V
Maximum Open Circuit Voltage:22 V
Extensive self-diagnostics
Optional redundancy
Supplies non-incendive field power
Suitable for Configure / Status for HART devices
HART-capable, multivariable instruments for
fastcollection of control variables
Fast loop scan
Non-Incendive Power
Voltage Rating:24 VDC
Module current rating:430 mA
Operating Temperature:0 to 60 °C
Storage temperature:-40 to 85 °C
Supervisory network type Series:8 PGM is a standard FTE node
Input Channels:32
Galvanic Isolation:1500 VAC RMS or ±1500 VDC
Isolation Technique:Optical (in IOM)
DI Power Voltage Range:18 to 30 VDC
ON Sense Voltage/Current :13 VDC (min) or 3 mA (min)
OFF Sense Voltage/Current :5 VDC (max) or 1.2 mA (max)
Input Impedance:4.2 K
Absolute Delay Across Input Filter and Isolation:5 ms ± 20%
Input Channels:16 Channels
A/D Converter Resolution:16 bits
Input Range:4-20 mA
Normal Mode Rejection Ratio, at 60 Hz:19 dB
Normal Mode Filter Response:Single-pole RC, -3 dB @ 6.5 Hz
Crosstalk, dc to 60 Hz:-60 dB
Maximum Input Voltage:± 30 Volts
Input Scan:Rate 50 ms