Input Module
Input16 group isolated and independent channels
Input Range (each channel)0 to 20.4 mA DC (each channel current limited to33 mA)
Accuracy (includes linearity)±0.03% of span
Accuracy temperature coefficient: ±50 ppm/° C
Common Mode Rejection>100 db at 50 or 60 Hz
Normal Mode Rejection>35 db at 50 or 60 Hz
Input Channel Impedance61.9 Ω nominal
INPUT VOLTAGE RANGE (REDUNDANT)24 V DC +5%, -10%
CONSUMPTION7 W (maximum) at 24 V DC11 W (maximum) at 24 V DC with all inputs at20.4 mA (internal power)
Analog Input Baseplate
Fault current130 mA,
typical200 mA, maximum
Current Input: 4–20 mA, 0–20 mA.
Voltage Input: 0–10 V DC, ±10 V DC
Resolution:16-bit resolution
Accuracy:±0.1% of full scale
Channel-to-channel isolation: 1500 V AC/DC
Operating Temperature:
-40°C to +70°C (-40°F to +158°F)
Storage Temperature:
-40°C to +85°C (-40°F to +185°F)
POWER MODULE
Support for 10 Mbps Ethernet trunk Fieldbus
Support for DIN rail mounted FBMs
Optional redundancy
Compact, rugged design
Easy to install and configure
Power Supply High Density Module
Chassis Type:Main/Expansion/RXM
Nominal Voltage:24 VDC
Input VAC @ 47-63 Hz:n/a
Input VDC:22-31
Fuse Rating and Type:15 amps, time-delay
Output Hold Time:2.8 ms minimum
Diagnostic Indicators:PASS, FAULT, ALARM, TEMP,BAT LOW
Fieldbus Communication Module
INPUT VOLTAGE RANGE (REDUNDANT)24 V dc +5%, -10%
CONSUMPTION7 W (maximum) at 24 V dc
HEAT DISSIPATION7 W (maximum) at 24 V dc
Vibration0.75 g (5 to 200 Hz)
TEMPERATURE-40 to +70°C (-40 to +158°F)
RELATIVE HUMIDITY5 to 95% (noncondensing)
ALTITUDE-300 to +12,000 m (-1,000 to +40,000 ft)
Network Communication Module
Input Voltage: 24 VDC
ower Consumption: 5 W
Modbus TCP/IP
Ethernet/IP
OPC (as applicable)

Copyright Notice © 2004-2024 amikong.com All rights reserved
Disclaimer: We are not an authorized distributor or distributor of the product manufacturer of this website, The product may have older date codes or be an older series than that available direct from the factory or authorized dealers. Because our company is not an authorized distributor of this product, the Original Manufacturer’s warranty does not apply.While many DCS PLC products will have firmware already installed, Our company makes no representation as to whether a DSC PLC product will or will not have firmware and, if it does have firmware, whether the firmware is the revision level that you need for your application. Our company also makes no representations as to your ability or right to download or otherwise obtain firmware for the product from our company, its distributors, or any other source. Our company also makes no representations as to your right to install any such firmware on the product. Our company will not obtain or supply firmware on your behalf. It is your obligation to comply with the terms of any End-User License Agreement or similar document related to obtaining or installing firmware.