Allowable input voltage ±5 V.
Withstanding voltage :1500 V AC for 1minute
Power ON 2 MΩ or more
Power OFF 2 MΩ or more
Accuracy ±0.03% of full scale (for 0 to 400 Ω)
Allowable total resistance of signalsource plus wiring:40 Ω or less
(wiring resistance per wire)
Temperature drift:Max. ±30 ppm/°C.
Maximum current consumption:450 mA (5 V DC)
Number of input channels:32
Rated input voltage:24 V DC
Input ON voltage:18 to 26.4 V DC
Input OFF voltage:5.0 V DC or less
Input current (at rated input voltage):4.1 mA±20 % / channel
Instantaneous allowable maximum input voltage:30.0 V DC
Input response time:8 ms or less
Minimum ON detection time:20 ms
Maximum ON/OFF cycle:25 Hz
Maximum current consumption:500 mA (5 V DC)
Number of output channels:64
Rated applied voltage:24 V DC
Load voltage:24 V DC, 100 mA
Field power supply voltagerange:20.4 to 26.4 V
Output ON voltage maximumvalue:2 V DC
Leak current maximum valuewhen output OFF:0.1 mA
Output format:Current sink
Number of input:channels16, non-isolated
Input signal:4 to 20 mA
Allowable input current/voltage:27 mA
Accuracy:±0.1% of full scale
Data refresh cycle:10 ms
Input step response time:100 ms
Transmitter power supply:22.8 to 26.4 V
Setting of 2-wire or 4-wiretransmitter
For each channel by setting pin
Series: Mark VIe
Channels: Configurable for 16–32 analog/digital channels
Analog: 4–20 mA, 0–10 V, RTD
Digital: 24 VDC dry/wet contacts
Supply Voltage: 24 VDC nominal
Power Consumption: Typically ≤ 8 W
Operating Temperature: -40°C to +70°C (-40°F to +158°F)
Series: Mark VI
Supply Voltage: Typically 24 VDC
Power Consumption: Varies by load
Operating Temperature: -40°C to +70°C
Humidity: 0–95% non-condensing