POWER SUPPLY BOARD
WITH JUMPER WIRE
Primary Input: 18–32 V DC
Backup Input: 24 V DC
Output Voltage: 24 V DC
Output Current: 6 A
Holdup Time: ≥48 hours
Efficiency: >85% (typical).
Ripple & Noise: <100 mV peak-to-peak
Compact installation of I/O modules
Up to 16 channels of field signals
and process power connections
Connections to ModuleBus and I/O modules
Mechanical keying prevents
insertion of the wrong I/O module
Latching device to DIN rail for grounding
DIN rail mounting
Function:32-Channel Analog Input Module
Voltage: ±10 V DC, 0–10 V DC
Current: 0–20 mA, 4–20 mA
Resolution:15 bits + sign
Accuracy:±0.1% of full scale @ 25°C
Update Time:8 ms (all channels)
Common-Mode Rejection:>120 dB @ 50/60 Hz
Overvoltage Protection:±35 V DC
Power Supply:24 V DC
LOGIC CONTROLLER
32 CHANNELS
18-30 VDC
2 VDC
OUTPUT RATING: 0.01 A MINIMUM
AT 24 VDC 1.0 A MAXIMUM
24 VDC CONTINUOUS
SURGE: 2.5 A PER CHANNEL
ISOLATION: 1K VDC
10 MA PER CHANNEL
16 channels for 24 V d.c.
Redundant or single configuration
Output status indicators
Advanced on-board diagnostics
Degraded mode for normally energized channels
Compact installations of I/O modules
Field signals and process power connections
Connections to ModuleBus and I/O modules
Mechanical keying prevents insertion of the wrong module
Latching device to DIN rail
DIN rail mounting
Input a.c. 100-240 V or d.c
110-150 V. Output
d.c. 24 V 20A
If redundant power application
is required connect to SS8XX voting unit
DIN rail mounted
G2 compliant
8 channels
The modules can be used in
both single and redundant applications
Interface for NAMUR, 12 V and
24 V transducer signal levels
Each channel can be configured for
pulse count or frequency measurement
The inputs can also be read as DI signals
Pulse count by accumulation in a 16 bit counter
Frequency (speed) measurement 0.5 Hz - 20 kHz
Advanced on-board diagnostics
Input impedance:2.5 kΩ
Maximum field cable length:200 meters (218 yards)
Rated insulation voltage:50 V
Dielectric test voltage:500 V a.c.
Power dissipation:2.5 W
Current consumption +5 V Modulebus:120 mA
NAMUR inputs
G3 compliant
Output status indicators
state upon error detection
Intrinsic Safety support
Short-circuit protection to ground and 30 V
8 channels with process voltage supervision
OSP sets outputs to predetermined
Over-voltage and over-temperature protection
3BSC690087R1
DISCONTINUED BY MANUFACTURER
INPUT MODULE
ANALOG
8 CHANNEL
4-20 MA
W/ INTRINSIC SAFETY INTERFACE
HART
(AO895)
Tariff Code: 85389091
Country of Origin: Singapore
Input/Output Type: Analog Output
Output Voltage:Typically 0-10 V DC or 4-20 mA
Channels:Typically 8 channels
Output Range:4-20 mA or 0-10 V
Output Accuracy:±0.1% of full scale
Power Supply:24 V DC
Power Consumption:Typically < 12 W
8 channels for 0...20 mA
4...20 mA, 0...5 V or 1...5 V d.c
single ended unipolar inputs
1 group of 8 channels isolated from ground
12 Bit resolution
Current limited transmitter supply per channel
HART pass-through communication
Clock Frequency: 48 MHz
Architecture: Typically a 32-bit
RAM:16–32 MB
Flash Memory: 64–128 MB
Voltage Range: Typically 24 V DC
Power Consumption: 5–10 W
Temperature Range: -40°C to +70°C
Humidity: 5–95% non-condensing.
Number of Input Channels: 8
Input Signal Type: 0 to 20 mA
Resolution: 12-bit
Input Impedance: 250 Ω
Nominal Input Current: 0 to 20 mA
Input Voltage Drop: Maximum 5V
Scanning Time: 10 ms per channel
Accuracy: ±0.1% of full-scale range
Isolation: Galvanic isolation between channels and system
Power Consumption: Typically 1.5 W
Operating Temperature: -25°C to +70°C