Response time :≥ 20 ms
Current input max. 0.6 A
Fuse (external) 10 A time-lag (T)
Back-up battery None
Operating voltage 24 VDC, -15...+20 %, rPP ≤ 15 %
Switching voltage 5 V, 250 VAC / 250 VDC
Number of channels 8 potential-free normally open contacts
Use in the PES H41q-MS, -HS, -HRS
Safety-related, applicable
up to SIL 3 according to IEC 61508
Microprocessors INTEL 386EX, 32 bits
Clock frequency 25 MHz
Data SRAM 1 MB
Space requirement 8 SU
Operating data 5 V / 2 A
Compact controller
with 24 digital inputs
8digital outputs
2 counters and 8 analog inputs
operating temperature -20...+60 °C
for SILworXprogramming tool
Number of outputs 8
Output voltage L+ minus 2 V
Minimum load 2 mA for each channel
Internal voltage drop max. 2 W at 2 A
Leakage current (with lowlevel)max. 1 mA at 2 V
Number of counters 2
Inputs 3 on each (A, B, Z)
100 Base-T interface, RJ45
Safe communication
(mono configuration or redundant)
between H41q/H51q
systems via safeethernet
Communication module for
the protocols safeethernet and
OPC DA via HIMA OPC server
Switching voltage ≥ 5 V, ≤ 250 V AC / ≤ 110 V DC
with integrated safety shutdown,
with safety isolation,
with 3 seriel relays (diversity)
solid state output (open collector)
for LED display in the cable plug
requirement class AK 1 ... 6
Model Number:F7541
Type:Safety I/O Connection Module
Safety Integrity Level:SIL 3
Channel Count:16 (8 redundant pairs)
Input Voltage Range:0-30V DC
Isolation Voltage:500V AC
Contact Rating:2A @ 30V DC
Power Consumption:1.5W