Interface Foundation fieldbus 4 ports
Transmission speed 31.25 kbps
field to system: 1500 V AC/minute
Max. 48 points/segment
Max. 32 units per segment
LAS function, Clock master function
DIGITAL INPUT MODULE
32 CHANNEL
24 VDC
ISOLATED
50 MA
PULSE WIDTH OUTPUT FUNCTION
TIME-PROPORTIONAL OUTPUT FUNCTION
STATUS DISPLAY
NO EXPLOSION PROTECTION
Number of input channels:64
Rated input voltage:24 V DC
Input ON voltage:20 to 26.4 V DC
Input OFF voltage :5.0 V DC or less
Input current :2.5 mA±20 % / channel
Maximum allowable input voltage:30.0 V DC
Input response time :8 ms or less
Minimum ON detection time:20 ms
Maximum ON/OFF cycle:25 Hz
Maximum current consumption:500 mA (5 V DC)
Number of inputs 16-channel, module isolation
Input signa:
No-voltage contact
ON: 1 kΩ maximum
OFF: 100 kΩ minimum
Input current 6 mA ± 20 %
Contact rating 24 V DC +20 % / -10 %
Input response time 40 ms maximum
Number of outputs 8-channel, module isolation
Output voltage 24 V DC
Output voltage drop 1 V maximum
External power supply rating 24 V DC, 5 A minimum
Maximum leak current at output offstatus 1.6 mA
Output format Current source
Maximum load current 0.6 A/output line
Minimum load current 35 mA
Load resistance range 40 to 685 Ω
Output response time 30 ms maximum
Input Voltage: 24 VDC
Operating Temperature: Typically 0°C to +60°C (32°F to 140°F)
Storage Temperature: -40°C to +85°C (-40°F to 185°F)
Humidity: 5% to 95% relative humidity
Supply Voltage:24 V DC
Current Consumption:Around 300 mA
Operating Temperature Range:-10°C to +55°C
Storage Temperature Range:-40°C to +70°C
Humidity:5% to 95%, non-condensing.