Channels: 32 analog input channels (AI)
and 32 digital input/output channels (DIO)
Signal types: Supports various analog and
digital signal types such as voltage,
current, temperature, pressure, and flow
Communication protocols: MODBUS® RTU,
FOUNDATION Fieldbus H1, HART®
Power supply: 24 VDC
Operating temperature: 0°C to 60°C
Number of inputs 16-channel, module isolation
Input current 6 mA ± 20 %
Contact rating 24 V DC +20 % / -10 %
External power supply 24 V DC +20 % / -10 %
Instantaneous maximum permissibleinput voltage 30.0 V DC
Input response time 40 ms maximum
Number of input channels 16 channels, module isolation
Rated input range 4 to 20 mA
Permissible input range 0 to 25 mA
Input impedance during Power-OFF 500 kΩ minimum
Data update frequency 40 ms
Temperature drift ±16 µA/10 °C
Withstand voltage 1.5 kV AC between input signal and system for 1 minute
8-channel, module isolation
24 V DC
1 V maximum
24 V DC, 3.4 A minimum
24 V DC + 20 % / -10 %
1.6 mA
0.2 A/output line (3.2 A in total output line) (*3) (*5)
120 to 685 Ω (*6
2 kV AC between output signal lines and system for 1 minute, 16-point input linescollectively connected (negative lines)
Number of inputs 16-channel, module isolation
Input current 6 mA ± 20 %
Contact rating 24 V DC +20 % / -10 %
External power supply 24 V DC +20 % / -10 %
Input response time 40 ms maximum
Withstand voltage (*1) (*2) 2 kV AC
between input signal and system for 1 minute
16-input line collectivelyconnected
Number of outputs 8-channel, module isolation
Output voltage 24 V DC
Output voltage drop 1 V maximum
External power supply rating 24 V DC, 5 A minimum
Maximum leak current at output offstatus 1.6 mA
Output format Current source
Minimum load current 35 mA
Load resistance range 40 to 685 Ω
Output response time 30 ms maximum
Interface Foundation fieldbus 4 ports
Transmission speed 31.25 kbps
field to system: 1500 V AC/minute
Max. 48 points/segment
Max. 32 units per segment
LAS function, Clock master function
DIGITAL INPUT MODULE
32 CHANNEL
24 VDC
ISOLATED
50 MA
PULSE WIDTH OUTPUT FUNCTION
TIME-PROPORTIONAL OUTPUT FUNCTION
STATUS DISPLAY
NO EXPLOSION PROTECTION
Number of input channels:64
Rated input voltage:24 V DC
Input ON voltage:20 to 26.4 V DC
Input OFF voltage :5.0 V DC or less
Input current :2.5 mA±20 % / channel
Maximum allowable input voltage:30.0 V DC
Input response time :8 ms or less
Minimum ON detection time:20 ms
Maximum ON/OFF cycle:25 Hz
Maximum current consumption:500 mA (5 V DC)
Number of inputs 16-channel, module isolation
Input signa:
No-voltage contact
ON: 1 kΩ maximum
OFF: 100 kΩ minimum
Input current 6 mA ± 20 %
Contact rating 24 V DC +20 % / -10 %
Input response time 40 ms maximum
Number of outputs 8-channel, module isolation
Output voltage 24 V DC
Output voltage drop 1 V maximum
External power supply rating 24 V DC, 5 A minimum
Maximum leak current at output offstatus 1.6 mA
Output format Current source
Maximum load current 0.6 A/output line
Minimum load current 35 mA
Load resistance range 40 to 685 Ω
Output response time 30 ms maximum
Input Voltage: 24 VDC
Operating Temperature: Typically 0°C to +60°C (32°F to 140°F)
Storage Temperature: -40°C to +85°C (-40°F to 185°F)
Humidity: 5% to 95% relative humidity
Supply Voltage:24 V DC
Current Consumption:Around 300 mA
Operating Temperature Range:-10°C to +55°C
Storage Temperature Range:-40°C to +70°C
Humidity:5% to 95%, non-condensing.
Voltage Rating: Up to 300V AC/DC
Current Rating: Up to 10A per channel
Isolation Voltage: 1500V AC between field and system
Contact Resistance: <50mΩ
Wire Size: Accepts 12-24 AWG
Material: Flame-retardant plastic housing
Dielectric Strength: 2000V AC for 1 minute
Five-Slot and Ten-Slot Module
configured to perform various functions,
Universal Stations in the TPS system.
Each module occupies a specific address (node)
on the Local Control Network (LCN).
Input Type:Thermocouple and / or RTD
Input channels:64 fully-isolated channel-to-channe
Input scan rate:1 Second fixed by IOM
Channel bandwidth:0 to 4.7 Hz (-3 dB)
Nominal input range:-20 to +100 millivolts
Temperature stability:+/-20 ppm per deg C max
Long term drift:500 ppm
Output Type:4-20 mA
Output Channels:16
Output Temperature Drift:0.005% of Full Scale/°C
Output Readback Accuracy:±4% of Full Scale
Output Current Linearity:± 0.05% of Full Scale nominal
Directly Settable Output Current Range:0 mA, 2.9 mA to 21.1 mA
Maximum Output Compliant Voltage:16 V
Maximum Open Circuit Voltage:22 V
Extensive self-diagnostics
Optional redundancy
Supplies non-incendive field power
Suitable for Configure / Status for HART devices
HART-capable, multivariable instruments for
fastcollection of control variables
Fast loop scan
Non-Incendive Power
Voltage Rating:24 VDC
Module current rating:430 mA
Operating Temperature:0 to 60 °C
Storage temperature:-40 to 85 °C
Supervisory network type Series:8 PGM is a standard FTE node
Input Channels:32
Galvanic Isolation:1500 VAC RMS or ±1500 VDC
Isolation Technique:Optical (in IOM)
DI Power Voltage Range:18 to 30 VDC
ON Sense Voltage/Current :13 VDC (min) or 3 mA (min)
OFF Sense Voltage/Current :5 VDC (max) or 1.2 mA (max)
Input Impedance:4.2 K
Absolute Delay Across Input Filter and Isolation:5 ms ± 20%
Input Channels:16 Channels
A/D Converter Resolution:16 bits
Input Range:4-20 mA
Normal Mode Rejection Ratio, at 60 Hz:19 dB
Normal Mode Filter Response:Single-pole RC, -3 dB @ 6.5 Hz
Crosstalk, dc to 60 Hz:-60 dB
Maximum Input Voltage:± 30 Volts
Input Scan:Rate 50 ms