System Display
Local or Remote Visual Indication
of 3500 Machinery Protection System
(4) Display Mounting Types
Up to (2) Displays per 3500 Rack
Input Signal: -10 Vdc to +10 Vdc
Power Consumption: 10.5 watts
Ethernet: 100Base-FX Fiber-Optic
Rack Interface Module
Power Consumption:4.75 watts, typical
Standard:RS232 serial communications
Data Rate:38.4 k baud
Normally closed contacts:Arc suppressors are provided
Maximum Current:<1 mA dc, Dry Contact to Common
Proximitor Monitor
Signal :Accepts from 1 to 4 proximitytransducer signals
Power consumption :7.7 Watts, typical
Standard I/O: 10 kΩ
Output Impedance:550 Ω
Transducer Power Supply:-24 Vdc
Gap filter:-3 dB at 0.09 Hz
Smax : 0.125 to 15.8 times runningspeed
VGA Display Monitor
System Event List
Alarm Event List
All module and channel data
3300 style rack view (API-670)
Current alarm data (quick view)
Nine custom display options
Proximitor I/O Module with Internal Terminations
(4) Channel Monitor
Internal terminations
Dual-level alarms (Alert/Danger)
Dynamic and static measurement
Various "Static Value" Parameters
Accepts Input from Proximity Transducers
Proximitor I/O Module with Internal Terminations
Vibration Transmitter
7 0 7.0 metres (23.0 feet)
0 2 Bulkhead screws
0 1 CSA Division 2
Power : Requires +12 to +35 Vdc
input at the transmitter terminal.
Maximum Loop Resistance :
1,000 Ω including cable at 35 Vdc.
Current Limiting : 23 mA typical.
Vibration Transmitter
7 0 7.0 metres (23.0 feet)
0 1 35 mm DIN rail clips
0 1 CSA Division 2
Power : Requires +12 to +35 Vdc
input at the transmitter terminal.
Maximum Loop Resistance :
1,000 Ω including cable at 35 Vdc.
Current Limiting : 23 mA typical
Vibration Transmitter
5 0 5.0 metres (16.4 feet)
0 2 Bulkhead screws
0 1 CSA Division 2
Power : Requires +12 to +35 Vdc
input at the transmitter terminal.
Maximum Loop Resistance :
1,000 Ω including cable at 35 Vdc.
Current Limiting : 23 mA typical.
Vibration Transmitter
5 0 5.0 metres (16.4 feet)
0 2 Bulkhead screws
0 0 Not required
Power : Requires +12 to +35 Vdc
input at the transmitter terminal.
Maximum Loop Resistance :
1,000 Ω including cable at 35 Vdc.
Current Limiting : 23 mA typical.
Vibration Transmitter
5 0 5.0 metres (16.4 feet)
0 1 35 mm DIN rail clips
0 5 CSA Division 2, ATEX Zone 0,
ATEXZone 2 and includes ABS maritimeapprova
Power : Requires +12 to +35 Vdc
input at the transmitter terminal.
Maximum Loop Resistance :
1,000 Ω including cable at 35 Vdc.
Current Limiting : 23 mA typical.
Vibration Transmitter
5 0 5.0 metres (16.4 feet)
0 1 35 mm DIN rail clips
0 1 CSA Division 2
Power : Requires +12 to +35 Vdc
input at the transmitter terminal.
Maximum Loop Resistance :
1,000 Ω including cable at 35 Vdc.
Current Limiting : 23 mA typical.
Vibration Transmitter
0 1 35 mm DIN rail clips
CN CSA Division 2, ATEX Zone 0,
ATEXZone 2 and includes ABS maritimeapproval
Power : Requires +12 to +35 Vdc
input at the transmitter terminal.
Maximum Loop Resistance :
1,000 Ω including cable at 35 Vdc.
Current Limiting : 23 mA typical.
Vibration Transmitter
0 4 0-4 mils pp (0-100 μm pp)
5 0 5.0 metres (16.4 feet)
0 1 35 mm DIN rail clips
0 5 CSA Division 2, ATEX Zone 0,
ATEXZone 2 and includes
ABS maritimeapproval
Power : Requires +12 to +35 Vdc
input at the transmitter terminal.
Maximum Loop Resistance :
1,000 Ω including cable at 35 Vdc.
Current Limiting : 23 mA typical.
Velomitor CT
Sensitivity 3.94 mV/mm/s (100 mV/in/s)±5%.
TemperatureSensitivity-8% to +5%
AmplitudeLinearity±2% to 63.5 mm/s pk
MountedResonantFrequency9 kHz, minimum
DynamicOutputImpedance<400 Ω typical
BroadbandNoise Floor 0.229 mm/s (0.009 in/s) pk.
OperatingTemperature-40 °C to +85 °C
StorageTemperature-40 °C to +100 °C
Shock Limit 5000 g pk, maximum.
HumidityLimit100% condensing
3300 XL 8 mm Probe
3300 XL 8 mm Probe
M10 x 1 thread
with armor
10 1.0 meter (3.3 feet)
01Miniature coaxial ClickLocconnector with connectorprotector,
standard cable
00 Not required
Order in increments of 10 mm
Length configurations:
Maximum unthreaded length: 230 mm
Minimum unthreaded length: 0 mm
Example: 0 6 = 60 mm
PROBE PROXIMITY VIBRATION 8MM
7200 5mm / 8mm Series
Proximity Transducer Systems
Frequency Response:
0 Hz (DC) to 10 kHz
Noncontacting
Gap-to-Voltage Transducer Systems
Measures Static and Dynamic Distances
PROBE PROXIMITY VIBRATION 8MM
Frequency Response:
0 Hz (DC) to 10 kHz
Noncontacting
Gap-to-Voltage Transducer Systems
Measures Static and Dynamic Distances
3300 XL 8 mm Proximity Probes
3300 XL 8 mm Probe
3/8-24 UNFthread
with armor
05 0.5 meter (1.6 feet)
02 Miniature coaxial ClickLocconnector,
standard cable
05 CSA, ATEX, IECEx Approvals
Order in increments of 0.1 in.
Length configurations:
Maximum unthreaded length: 8.8 in.
Minimum unthreaded length: 0.0 in.
Example: 0 4 = 0.4 in.
3300 NSv Extension Cable
060 6.0 meters (19.7 feet)
03 Without stainless steel armor
with connector protector
05 Multiple Approvals
3300 NSv Proximity Probes
3300 NSv Probe
M10X1 thread
without armor
05 0.5 meter (20 in)
02 Miniature coaxial ClickLoc connector,
standard cable
00 Not required
3300 XL NSv Proximity Transducer
3300 NSv Probe
M8X1 thread
without armor
10 1.0 meter (39 in)
02 Miniature coaxial ClickLoc connector
standard cable
05 Multiple Approvals
Order in increments of 10 mm.
Length configuration:
Maximum unthreaded length:230 mm
Minimum unthreaded length:0 mm
Example:06 = 60 mm
Vibration Transmitter
10 0-10 mils pp (0-250 μm pp)
70 7.0 meters (23.0 feet)
01 35 mm DIN rail clips
00 Not required
Operating temperature
-35°C to +85°C(-31°F to +185°F)
Storage temperature
-52°C to +100°C(-62°F to +212°F).
Probe Cable 75Ω coaxial,
fluoroethylenepropylene (FEP) insulated
NSv Proximitor Sensor
3300 NSv Probe
3/8-24 UNF thread
withoutarmor
5.0 metre (16.4 feet) systemlength
panel mount
0 0 Not required
NSv Proximity Sensor
7.0 5.9 ± 0.9
Extension cabledc resistance
Center conductor: 0.220Ω/m (0.067 Ω/ft)
RecommendedGap Setting 1.0 mm (40 mils)
IncrementalScale Factor 7.87 V/mm (200 mV/mil)
OperatingTemperature-52°C to +177°C
StorageTemperature-52°C to +177°C (-62°F to+351°F)
System Rack
Holds All 3500 Monitor Modules
Rack Power Supplies
Manufactured in (2) Sizes:
Full-Size Rack and Mini-Rack
Manufactured in (3) Formats:
Panel Mount, Rack Mount, and Bulkhead Mount
7 or 14 Rack Postitions

Copyright Notice © 2004-2024 amikong.com All rights reserved
Disclaimer: We are not an authorized distributor or distributor of the product manufacturer of this website, The product may have older date codes or be an older series than that available direct from the factory or authorized dealers. Because our company is not an authorized distributor of this product, the Original Manufacturer’s warranty does not apply.While many DCS PLC products will have firmware already installed, Our company makes no representation as to whether a DSC PLC product will or will not have firmware and, if it does have firmware, whether the firmware is the revision level that you need for your application. Our company also makes no representations as to your ability or right to download or otherwise obtain firmware for the product from our company, its distributors, or any other source. Our company also makes no representations as to your right to install any such firmware on the product. Our company will not obtain or supply firmware on your behalf. It is your obligation to comply with the terms of any End-User License Agreement or similar document related to obtaining or installing firmware.